Performance of Single Pass Earth-Tube Heat Exchanger: An Experimental Study


237 / 4

Authors

  • Girija Sharan Coordinator, Cummins-IIMA Lab, Centre for Mgt in Agriculture, Indian Institute of Management, Ahmedabad.
  • Ratan Jadhav Project Officer, SEWA, Ahmedabad, Gujarat

Abstract

A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in cooling and heating modes. ETHE consisted of 50 m mild steel pipe of 10 cm nominal diameter and 3 mm wall thickness, buried 2.85 m deep below ground. Ambient air was pumped through it for conditioning. Tests were conducted on three consecutive days in each month. The ETHE conditioned 5.6 m³/min of 40.6degree C air to 26.6degree C in cooling mode, and 8.3degree C air to 23.0degree C in heating mode. Average COP was 3.3 in cooling and 3.8 in heating mode.